Power calculator
Solve any V·I·P·R combination for direct current, single-phase AC, or three-phase AC. Returns active power (W / kW), apparent (kVA), reactive (kVAR), horsepower, BTU/hour. Step-by-step formula trace and PDF report. Reviewed by a licensed PE.
Use the power calculator
Pick the phase mode at the top, then choose which two values you have ("I know:") — V&I, V&P, V&R, I&P, I&R, or P&R. The other two compute live, with apparent power, reactive power, HP, and BTU/hr in the detail panel.
Pure DC: P = V · I. Resistance shown is V/I (Ohm's law equivalent).
- Apparent power S
- — kVA
- Reactive power Q
- — kVAR
- Power factor used
- —
- Mechanical equivalent
- — HP
- Heat output
- — BTU/hr
P = V · I = ... The power formula
One formula covers DC, two cover AC — the only difference is the cos φ correction (single-phase AC) and the additional √3 factor (three-phase line-to-line). Solving for current or resistance is just rearranging the equation.
- P
- electrical power, W
- V
- voltage, V
- I
- current, A
- R
- resistance, Ω
- P
- active (real) power, kW, W
- S
- apparent power, kVA, VA
- Q
- reactive power, kVAR, VAR
- cos φ
- power factor (1.0 for resistive), —
- V_LL
- line-to-line voltage, V
- I
- line current, A
Worked example: 50 HP three-phase motor on 480 V
A 50 HP industrial motor running on a 480 V three-phase service at 0.85 power factor and 92% efficiency. Compute kW input, FLA (full-load amps), and the kVA the transformer must supply.
| Quantity | Calculation | Result |
|---|---|---|
| Output power | 50 HP × 745.7 | 37 285 W = 37.3 kW |
| Input power (electrical) | P_out / efficiency = 37.3 / 0.92 | 40.5 kW |
| Apparent power | kVA = kW / PF = 40.5 / 0.85 | 47.6 kVA |
| Full-load amps (FLA) | I = kVA × 1000 / (√3 × V) = 47 600 / (1.732 × 480) | 57.3 A |
| Reactive power | Q = √(S² − P²) = √(47.6² − 40.5²) | 25.0 kVAR |
| Annual energy at 50% duty | 40.5 × 8760 × 0.5 | 177 MWh / yr |
How to calculate power, step by step
- Identify what you know. Pick any two of {voltage V, current I, power P, resistance R}. The other two follow from Ohm's Law and the power equation.
- Pick the phase mode. DC for batteries and pure-resistance loads. Single-phase AC for residential mains. Three-phase AC for commercial / industrial service. The √3 factor enters only for three-phase.
- For AC, set the power factor cos φ. Pure resistive (heaters, incandescent lamps) → cos φ = 1.0. Motors typically 0.80–0.90. Highly inductive loads (welders, fluorescent ballasts) 0.50–0.75. Power factor connects active and apparent power: P = S × cos φ.
- Apply the formula. P = V·I (DC), P = V·I·cos φ (1-phase), P = √3·VLL·I·cos φ (3-phase). Solve for the missing variable algebraically — or use the calculator above.
- Convert to other units if needed. Watts → kilowatts (÷1000), HP (÷745.7), BTU/hr (×3.412). Apparent power S = V·I (1ph) or √3·V·I (3ph), in volt-amps. Reactive Q = √(S² − P²), in VAR.
- Sanity-check against the device nameplate. Motor nameplate gives FLA (full-load amps), HP, V, PF, efficiency. Computed kW from those values should match within 5–10%; bigger discrepancy suggests wrong PF or efficiency assumption.
Reference table — typical loads
| Equipment | Power | 120V 1ph A | 240V 1ph A | 480V 3ph A |
|---|---|---|---|---|
| LED lamp | 10 W | 0.08 | 0.04 | — |
| Laptop charger | 65 W | 0.54 | 0.27 | — |
| Refrigerator (running) | 150 W | 1.25 | 0.63 | — |
| Microwave | 1200 W | 10.0 | 5.0 | — |
| Electric kettle | 1500 W | 12.5 | 6.25 | — |
| Air conditioner (12 kBTU) | 1200 W | 10.0 | 5.0 | — |
| Electric oven (range) | 5000 W | — | 20.8 | — |
| EV Level 2 charger | 7200 W | — | 30 | — |
| 5 HP motor | 3.7 kW (out) | — | 28 | 7.6 |
| 25 HP motor | 18.7 kW (out) | — | — | 34 |
| 100 HP motor | 74.6 kW (out) | — | — | 124 |
Active vs apparent vs reactive power
| Quantity | Symbol | Unit | Physical meaning | Where it appears |
|---|---|---|---|---|
| Active (real) power | P | W / kW | Energy actually used (heat, light, work) | Utility billing, motor output, equipment ratings |
| Apparent power | S | VA / kVA | V × I (RMS), no PF correction | Transformer / UPS / generator sizing |
| Reactive power | Q | VAR / kVAR | Stored/returned by L and C each cycle | PF correction, capacitor bank sizing |
| Power factor | cos φ | — | Ratio P / S | Utility PF penalty above 0.85 |
| Mechanical power | HP / kW | HP or W | Motor shaft output (P_in × η) | Motor selection, gear sizing |
Variants and special cases
DC power
Pure resistive: P = V·I, no power factor. Used for battery systems, solar PV, EVs, USB. Energy in batteries: Wh = Ah × V.
Single-phase AC power
P = V·I·cos φ for active, S = V·I for apparent. Standard residential mains worldwide; cos φ depends on connected loads (mostly resistive in homes).
Three-phase AC power (balanced)
P = √3·VLL·I·cos φ. Used for nearly all commercial and industrial service. Power flow is constant in time (smoother than single-phase ripple).
Apparent power and the kVA rating
Transformers, UPS systems, and generators are rated in kVA, not kW — they must supply the full apparent power regardless of PF. A 100 kVA transformer can deliver 100 kW only at PF = 1.0; at PF 0.7 it delivers 70 kW (but still 100 kVA worth of current).
Reactive power and the power triangle
P, Q, and S form a right triangle: S² = P² + Q², φ = arctan(Q/P). Capacitive Q is conventionally negative (current leads voltage); inductive Q is positive (current lags). The triangle is the geometric basis for power-factor correction.
Mechanical horsepower
1 HP = 745.7 W (US) or 735.5 W (metric PS). HP from torque: HP = T(lb-ft) × RPM / 5252. Motor shaft HP equals input kW × efficiency, where η is typically 0.85–0.95.
RMS vs instantaneous power
For sinusoidal AC, instantaneous power oscillates at 2× line frequency between 0 and peak. The "average power" or "RMS power" reported by all standard meters is what the equations compute. Don\'t confuse RMS power with peak power — the latter is double.
Power in capacitors and inductors
Pure capacitors and inductors store and release energy without net dissipation. Their average active power is zero; their reactive power is significant. This is why filters can be lossless but still affect circuit behaviour.
Power loss in conductors
Conductor power loss P_loss = I² × Rcable, dissipated as heat. For a 30 m run of 10 AWG Cu carrying 20 A: R ≈ 0.1 Ω, P_loss ≈ 40 W — small compared to a typical load but it adds up across long runs and motivates voltage-drop limits. See Voltage Drop Calculator.
Power quick reference — torque, horsepower, 3-phase, amps
| Topic / question | Quick answer |
|---|---|
| 3 ph power calculation / 3 phase ac power calculation | P = √3 × V_LL × I × cos φ. For 480 V × 100 A × PF 0.9: P = 1.732 × 480 × 100 × 0.9 = 74.8 kW. The same calculator above does this when you switch phase mode to "3-phase". |
| Torque to horsepower / torque to power / power to torque formula | HP = (τ_lb-ft × RPM) / 5252; rearranged, τ = HP × 5252 / RPM. In SI: P (kW) = (τ_Nm × RPM) / 9550. The torque-to-power relationship is bidirectional — same equation, solved for the missing variable. |
| Torque to horsepower calculator / horsepower torque calculator / horsepower and torque calculator / torque and horsepower calculator / horsepower calculator torque / horsepower calculator from torque | All these queries describe the same conversion: enter torque (lb-ft or N·m) and shaft speed (RPM) → returns horsepower (or kW). The PowerCalc engine above includes a torque mode; alternatively use the dedicated RPM / torque calculator. |
| Torque horsepower formula / torque horsepower equation / power torque formula / power torque equation / horsepower to torque equation / horsepower to torque formula / power equation torque / power formula torque / torque power formula / torque power equation | One equation in many phrasings: HP × 5252 = torque (lb-ft) × RPM. Memorise this and every torque-power question above is one rearrangement away. |
| Horsepower amperage calculator / amps horsepower calculator / amps to horsepower calculator / convert horsepower to amps | I = (HP × 746) / (V × η × cos φ) for a single-phase motor; divide by an additional √3 for three-phase. For a 50 HP, 480 V, 3-φ motor with η = 0.92 and PF 0.85: I = (50 × 746) / (1.732 × 480 × 0.92 × 0.85) = 57.4 A. NEC Table 430.250 is the code-compliant lookup for branch sizing. |
| Power formula calculator / power formulas calculator / power calculator formula | The PowerCalc above is a power formula calculator: enter any two of voltage, current, resistance, or power and it solves the other two — plus apparent (kVA), reactive (kVAR), horsepower, and BTU/hr equivalents. |
| Power supply | A device that converts wall AC into the regulated DC voltage equipment needs. The power supply rating in watts (or VA) sizes the upstream branch circuit; rule of thumb is a 1.25× safety margin on the continuous load current. |
Related concepts on this site
Frequently asked questions
- How do you calculate power?
- Three forms depending on the system. DC: P = V × I. Single-phase AC: P = V × I × cos φ (active power, kW). Three-phase AC: P = √3 × VLL × I × cos φ. Example: 120 V × 10 A DC = 1200 W. Same on AC at PF 0.85: 120 × 10 × 0.85 = 1020 W active. Use the calculator above with the right phase mode for your case.
- How to calculate horsepower from torque?
- HP = (Torque × RPM) / 5252 with torque in lb-ft, RPM in revolutions per minute. The 5252 constant comes from 33000 ft-lb/min per HP divided by 2π. Example: 100 lb-ft of torque at 3600 RPM = 100 × 3600 / 5252 = 68.5 HP. In SI units: HP = (Nm × RPM) / 7121, or P (kW) = (Nm × RPM) / 9550. This is also the answer to "how horsepower is calculated" from a measured torque and shaft speed.
- How to calculate torque from horsepower?
- Inverse of the above: Torque (lb-ft) = HP × 5252 / RPM. Example: a 50 HP motor at 1800 RPM produces 50 × 5252 / 1800 = 146 lb-ft of torque. Two motors of equal HP can have very different torque depending on RPM — a slow-turning motor produces more torque, which is why high-torque applications use gear reducers to trade RPM for torque.
- How to measure DC power?
- Two instruments: a DC voltmeter across the load (measures V) and a DC ammeter in series (measures I). DC power P = V × I, no power factor. For accurate reading at high power, use a Hall-effect or shunt-resistor current sensor; for very low power, use a four-wire (Kelvin) connection to eliminate lead resistance. Multimeters with simultaneous V/I display make this routine — or use a dedicated DC power meter that integrates over time to also report energy (Wh).
- What is the difference between active, apparent, and reactive power?
- Active power (P, watts) is the real work being done — heat, light, mechanical output. Reactive power (Q, VAR) is shuffled between source and reactive components (inductors, capacitors) without doing net work. Apparent power (S, VA) is the geometric sum: S = √(P² + Q²). The relationship cos φ = P/S defines power factor. Utilities bill on active power (kWh) but penalise low PF because reactive current still loads the conductors.
- How is power related to energy?
- Power is the rate of energy use; energy is power × time. Units: 1 watt-hour (Wh) = 3600 joules of energy. kWh = kW × hours. A 1.5 kW heater run for 4 hours uses 6 kWh of energy. Utility billing is in kWh. To estimate operating cost: kWh × electricity rate ($/kWh) = $ per period. The calculator above shows instantaneous power (W); multiply by your duty cycle (hours per day, days per year) to get energy.
- What is power factor and why does it matter?
- Power factor cos φ = P/S, the ratio of active to apparent power. PF = 1.0 means all current is doing useful work; PF = 0.7 means 30% of the current is "wasted" cycling reactive energy. Low PF still loads conductors and transformers, so utilities charge a PF penalty above ~0.85 demand. Industrial loads (motors) are typically 0.80–0.85 PF; capacitor banks can correct this back toward 1.0 — see Power Factor calculator.
Sources and methodology
- Ohm, G. S. Die galvanische Kette, mathematisch bearbeitet, 1827.
- IEEE. IEEE Std 100 — Authoritative Dictionary of IEEE Standards Terms, 7th Edition.
- NFPA. NEC 70 — National Electrical Code, 2023. Article 100 (definitions), 430.250 (motor FLA).
- BIPM. The International System of Units (SI), 9th Edition, 2019.
- Steinmetz, C. P. Theory and Calculation of Alternating Current Phenomena, McGraw-Hill, 1897.