SCALE 1:1 STD NEC · IEC · AS/NZS · ACI · AISC
B
CodePass.PRO
Engineering Calculators
SHEET 33 / 79
Reference · Lookup · NEC 240.6 · UL 489 · MCA / MOP

Circuit Breaker Sizes — Standard Ratings & Wire Pairing Reference

Standard circuit breaker sizes are listed in NEC §240.6 — 15 A to 6000 A, with the residential / light-commercial range running 15 to 200 A. This page covers the wire-size pairing chart, AC-unit MCA / MOP rules, AIC ratings, MCB vs MCCB vs LV power breakers, dead-tank vs live-tank distinction for transmission breakers, inverse-time tripping curves, and worked sizing examples for an AC compressor and a sub-panel feeder. Reviewed by a licensed PE.

Circuit breaker calculator and tools

For motor and HVAC branch-circuit sizing, the site MCA / MOP calculator computes Minimum Circuit Ampacity and Maximum Overcurrent Protection for AC units per NEC §440. The wire-size calculator confirms the conductor pairing; the short-circuit calculator validates the AIC rating against available fault current at any panel location.

→ MCA / MOP calculator (HVAC AC units)  ·  → Wire size calculator  ·  → Short-circuit calculator  ·  → IDMT inverse-time relay calculator

Circuit breaker sizing formulas

Eq. 01 — Continuous-load breaker sizing (NEC §210.20) SI
Ibreaker1.25Icont+InoncontI_{breaker} \geq 1.25 \cdot I_{cont} + I_{non-cont}
·
I_cont = load operating ≥ 3 hr at maximum amperes
·
I_non-cont = intermittent load
·
Round up to next standard size (NEC §240.6)
Eq. 02 — Motor branch breaker (NEC §430.52) SI
Ibreaker=2.50IFLAI_{breaker} = 2.50 \cdot I_{FLA}
·
For inverse-time circuit breakers protecting standard squirrel-cage motors
·
Different multiplier for instantaneous trip (8.0×), HACR (1.75×), or fuse (1.75–3.00×)
·
I_FLA from NEC Table 430.250 (3-phase) or 430.248 (1-phase)
Eq. 03 — AC unit MOP (NEC §440.22) SI
IMOP1.75RLA+1.0IfanI_{MOP} \leq 1.75 \cdot RLA + 1.0 \cdot I_{fan}
·
RLA = Rated Load Amperes from AC nameplate (compressor + ECM fan motors)
·
I_fan = sum of other motors on the branch
·
Round up to next standard size, but never exceed 225 % RLA
Eq. 04 — Available fault current and AIC rating SI
AICbreakerIfault,availableAIC_{breaker} \geq I_{fault, \, available}
·
AIC = breaker's interrupting rating (10 kA, 22 kA, 65 kA…)
·
I_fault = available short-circuit current at the breaker location
·
NEC §110.9 — equipment must be marked with AIC ≥ available fault current

Standards governing circuit breakers

DocumentScope
NFPA 70 (NEC) §240.6Standard ampere ratings — fuses and inverse-time circuit breakers
NEC §240.4 / §240.4(D)Conductor protection — small conductor rule (#14 → 15 A, #12 → 20 A, #10 → 30 A)
NEC Article 430 / §430.52Motor branch overcurrent — multipliers for breaker, fuse, instantaneous
NEC Article 440 / §440.22HVAC AC units — MCA / MOP rules
UL 489Molded-case circuit breakers (the residential / commercial workhorse)
UL 943GFCI breakers — 4–6 mA trip threshold
UL 1699AFCI breakers — series + parallel arc detection
IEC 60898 / IEC 60947-2European MCB / MCCB performance and test standard
IEEE C37.13 / .14Low-voltage AC power circuit breakers (drawout LV switchgear)

Reference: standard breaker sizes vs. wire size

Breaker (A)Cu wire (NEC 310.16, 75 °C)Al wireTypical use
1514 AWG12 AWGLighting, outlets in dwellings
2012 AWG10 AWGKitchen, bath, garage outlets
3010 AWG8 AWGDryer, A/C, water heater
408 AWG6 AWGRange, large A/C
506 AWG4 AWGEV charger, range, sub-panel
606 AWG4 AWGSub-panel feeder, hot tub
704 AWG3 AWGSub-panel feeder
804 AWG3 AWGIndustrial branch
903 AWG2 AWGIndustrial branch
1003 AWG1 AWGSub-panel main
1251 AWG2/0 AWGService feeder
1501/0 AWG3/0 AWGSquare D QO panel main
1752/0 AWG4/0 AWG200 A service derate area
2003/0 AWG250 kcmilStandard residential service
2254/0 AWG300 kcmilLight commercial service
400500 kcmil700 kcmilCommercial main
  1. Determine the load Branch lighting / receptacle: count fixtures and outlets per NEC §220.14. Single appliance: nameplate amperes. Motor: NEC Table 430.250 FLA. AC unit: nameplate MCA (Minimum Circuit Ampacity) and MOP (Maximum Overcurrent Protection) per UL 1995 / AHRI rating.
  2. Apply the continuous-load factor NEC §210.20: required breaker rating = 1.25 × continuous load + 1.0 × non-continuous. Most commercial / industrial branches and any branch operating 3+ hours at full load qualify.
  3. Round up to next standard size NEC §240.6 lists standard inverse-time breaker sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200 A. Always round up.
  4. Verify the conductor matches Conductor ampacity (NEC 310.16, 75 °C column) must equal or exceed breaker size for general circuits, OR satisfy the small-conductor rule (NEC §240.4(D)) for AWG ≤ 10. Mismatched wire / breaker is the most common code violation.
  5. Verify the AIC rating Available short-circuit current at the breaker location (per NEC §110.10) must not exceed the breaker's interrupting rating (AIC). Residential QO / Homeline = 10 kA standard, 22 kA in -H variants. Commercial PowerPact / Square D HJL frame = 25–65 kA depending on size.

Worked example — 5-ton residential AC condenser

Trane XR16 5-ton condenser. Nameplate: RLA = 22.5 A, fan motor 1.5 A, MCA = 29.6, MOP = 50 A, 240 V single-phase.

  1. Conductor sizing per MCA: 29.6 A → 10 AWG Cu THHN (35 A at 75 °C) is sufficient.
  2. Breaker per MOP: Use 50 A maximum — but typically install the smallest standard size at or below MOP that protects the conductor. For 10 AWG: NEC §240.4(D) limits to 30 A → so even though MOP allows 50 A, conductor limits to 30 A. Use 30 A breaker, OR upsize to 8 AWG and use the 50 A MOP rating.
  3. Recommended: 8 AWG Cu THHN (50 A) + 50 A breaker — uses the full MOP allowance and matches the manufacturer nameplate.
  4. AIC verification: Residential service typically < 10 kA available — standard QO 10 kA breaker satisfies NEC §110.9.

Comparison — MCB vs. MCCB vs. LV power circuit breaker

AspectMCB (Miniature)MCCB (Molded-case)LV Power CB (drawout)
StandardUL 489 / IEC 60898UL 489 / IEC 60947-2IEEE C37.13 / .14
Ampere range0.5 – 125 A15 – 2500 A800 – 6000 A
AIC range5 – 25 kA10 – 200 kA50 – 200 kA
Trip typeThermal-magneticThermal-magnetic, electronicElectronic LSIG (long, short, instant, ground)
MountingPlug-on or DIN-railBolt-on or plug-onDrawout (manually rolled in/out)
Best forResidential, light commercialCommercial, light industrialHeavy industrial, switchgear bus

Variants and related queries

Breaker — the full family

"Breaker" is industry shorthand for circuit breaker. The product family stretches from 0.5 A miniature DIN-rail units through 6000 A drawout switchgear breakers. UL 489 is the standard most US engineers cite; IEC 60898 (residential MCB) and 60947-2 (industrial MCCB) cover the international market. All share the same fundamental architecture: a switching mechanism, a thermal element (overload), a magnetic element (short-circuit), and an arc-quenching chamber.

Dead-tank vs. live-tank circuit breakers (transmission)

For high-voltage transmission breakers (72.5 kV and up), the "tank" refers to the metal enclosure containing the interrupter. In a dead-tank design, the tank is at ground potential and the bushings carry conductor-grade voltage to the contacts inside. In a live-tank design, the tank itself is at line potential and only insulators between tank and ground carry the voltage drop. North American practice favours dead-tank (Square D / GE / Siemens 72.5–245 kV); European practice often uses live-tank designs.

Inverse-time circuit breaker

An inverse-time breaker has trip time that decreases as overcurrent magnitude increases. Mild overload (110 %) takes hours; severe overload (500 %) takes cycles; short circuit (10× rating) takes milliseconds via the magnetic element. The thermal element produces the inverse curve and resets after the breaker cools (typically 5–15 minutes). This behaviour is what NEC §430.52 references when sizing motor branch breakers — the inverse curve allows starting inrush without nuisance tripping while still protecting the conductor on a sustained overload.

Type C circuit breaker (and B, D)

European IEC 60898 MCBs are sold in trip curves B (3–5× pickup), C (5–10×), D (10–20×). Type B for resistive loads; type C for general lighting and general motor loads (most common); type D for transformer inrush and high-magnetising-current loads. The North American UL 489 equivalent uses HACR (Heating, Air Conditioning, Refrigeration) and standard inverse-time as the rough analogue.

3-phase breaker (AC) and 240 V breaker

A 3-phase breaker is a triple-pole unit with one toggle that interrupts all three phases simultaneously — required by NEC §240.20(B) for any three-phase load. A 240 V single-phase residential breaker is double-pole — two single-pole breakers ganged with a common trip bar. Both ensure phase isolation: a fault on one pole trips all poles, preventing single-phasing of motors or partial energisation of equipment.

20 amp twin (tandem) breaker

A "twin" or "tandem" breaker fits two single-pole breakers into one slot of the panel. UL-listed only for panel positions marked "tandem-OK"; using them in non-listed positions violates §110.3(B). Useful when a panel is full and a small new circuit must be added without service replacement, but the practice is discouraged in new construction.

Frequently asked questions

How to size a circuit breaker?
Five steps. (1) Compute load — continuous + non-continuous. (2) Apply 1.25 × continuous-load factor per NEC §210.20. (3) Round up to next standard size from NEC §240.6 (15, 20, 30, 40, 50, 60, 70, 80, 100, 125, 150, 200…). (4) Confirm conductor ampacity (NEC 310.16, 75 °C column) ≥ breaker rating, except for the small-conductor rule (#14 limited to 15 A, #12 to 20 A, #10 to 30 A regardless of ampacity). (5) Verify breaker AIC rating ≥ available fault current at the breaker location. The wire-size and MCA/MOP calculators handle steps 1–4 automatically.
How to wire a 240v breaker?
A 240 V single-phase double-pole breaker takes two hot conductors (one to each pole), a neutral if the appliance needs 120 V too, and an equipment grounding conductor. Strip 5/8 in of insulation, land each hot under its breaker lug torqued per the manufacturer (typically 20 in-lb for QO 20 A, up to 250 in-lb for 200 A frames). Land the neutral on the neutral bar, the EGC on the ground bar. Snap the breaker onto the bus stab, restore the main, and verify 240 V hot-to-hot and 120 V each hot-to-neutral. For 240 V-only loads (range, dryer, EV charger), the neutral may be optional — check appliance instructions.
How to install a 240v breaker?
Same as above, with two additional steps before powering up. (1) Lock-out / tag-out the main service disconnect and verify zero voltage at the bus with a non-contact tester. (2) Open the deadfront panel cover and identify two adjacent unused breaker positions on opposite phases (in a residential single-phase panel, alternating bus stabs are connected to phase A and phase B; double-pole breakers must straddle one of each). Then strip, torque, snap-in, restore main, and verify with a meter.
How to replace a fuse in a circuit breaker?
Modern breakers do not contain replaceable fuses — they contain a thermal bimetal element and a magnetic coil that work together to detect overload and short-circuit. If you have an old "fuse panel" instead, the screw-in fuses (Type S Edison-base or cartridge fuses) can be replaced one-for-one after de-energising. If a modern breaker fails to reset (handle springs back to "tripped" or rests in centre), it has internal damage and must be replaced as a unit — there are no user-serviceable parts inside.
What is inverse time circuit breaker (inverse-time)?
An inverse-time circuit breaker has a trip time that decreases as the overcurrent magnitude increases. Mild overload (110 % of rating) takes hours to trip; severe overload (500 %) trips in cycles; short circuit (>10× rating) trips in milliseconds via the magnetic element. Standard "inverse-time" thermal-magnetic breakers cover the residential and light-commercial market. The IDMT relay calculator at /relay/ computes trip time for industrial protection relays that follow the same inverse-time philosophy.
What does a dead circuit breaker look like?
A failed (dead) breaker typically shows one of these symptoms: handle stuck in the "tripped" centre position and won't reset, handle in "ON" position but no voltage on the load terminals, audible hum or buzz from the breaker, scorch marks on the breaker face or surrounding panel paint, melted plastic around the lug, or warm-to-hot breaker case at low load. Any of these warrants immediate replacement — do not attempt to repair. De-energise the panel, swap in an identical-rated breaker from the same manufacturer's catalogue.

Historic source — invention of the modern circuit breaker

Stotz combined a bimetallic thermal element (for slow overload) with a magnetic coil (for fast short-circuit), then added a snap-action mechanism so the contacts open faster than the operator\'s hand can move them. The combination became the foundation of every miniature circuit breaker manufactured since.

Hugo Stotz — Patent DE 458 509 (1924) → Thermal-magnetic miniature circuit breaker — the architecture every modern UL 489 / IEC 60898 breaker still uses

Related calculators and references

Sources and further reading

  1. NFPA 70 — NEC, §240.4, §240.6, §210.20, Article 430, Article 440 (2023 edition).
  2. UL 489 — Standard for Molded-Case Circuit Breakers, current edition.
  3. UL 943 — GFCI; UL 1699 — AFCI; UL 1077 — supplementary protectors.
  4. IEC 60898-1 — European MCB performance; IEC 60947-2 — industrial MCCB.
  5. IEEE C37.13 / C37.14 — low-voltage AC power circuit breakers.
  6. Square D / Schneider Electric — Power Distribution Engineering Reference Manual.

Site

© 2026 · Engineering Calculators