SCALE 1:1 STD NEC · IEC · AS/NZS · ACI · AISC
B
CodePass.PRO
Engineering Calculators
SHEET 21 / 79
Calculator · Electrical · Fortescue 1918 · IEEE Std 1159 · NEMA MG 1

Unbalanced 3-phase calculator

Decomposes any unbalanced three-phase voltage set into the three Fortescue symmetrical components — zero-sequence, positive-sequence, and negative-sequence — and computes the voltage unbalance factor by both NEMA and IEEE definitions. Used to diagnose motor heating, ground faults, and power-quality problems. Reviewed by a licensed PE.

Use the calculator

Enter the magnitude (V) and angle (degrees) of each line-to-neutral voltage. The calculator returns V₀, V₁, V₂ in polar form and the voltage unbalance factor by both NEMA and IEEE definitions. Warnings appear at 2 % and 5 % thresholds per NEMA MG 1.

CALC.019 3-Phase · Power · Y/Δ · Unbalanced · NEC 430 Motor
Unbalanced 3-phase — symmetrical components

Enter phase magnitudes (V) and angles (degrees) for the three line-to-neutral voltages.

Symmetrical components per Fortescue 1918: any unbalanced 3-phase set decomposes into V₀ (zero-seq, ground-fault current), V₁ (positive-seq, useful power), V₂ (negative-seq, motor heating).

Result
— kW
Pick a mode and enter values.
FORMULA · S = √3 · V_LL · I SOURCE · NEC 430 · IEEE STD 100 · FORTESCUE 1918

The four symmetrical-component formulas

Eq. 01 — Fortescue decomposition SI · Fortescue 1918
[V0V1V2]=13[1111aa21a2a][VaVbVc]\begin{bmatrix}V_{0}\\V_{1}\\V_{2}\end{bmatrix} = \frac{1}{3}\begin{bmatrix}1&1&1\\1&a&a^{2}\\1&a^{2}&a\end{bmatrix} \begin{bmatrix}V_{a}\\V_{b}\\V_{c}\end{bmatrix}
a
unit phasor at 120°: a = e^(j·120°), —
V₀
zero-sequence, V
V₁
positive-sequence, V
V₂
negative-sequence, V

The three symmetrical components are linear combinations of the three original phase voltages. Reverse: V_a = V₀ + V₁ + V₂; V_b = V₀ + a²·V₁ + a·V₂; V_c = V₀ + a·V₁ + a²·V₂. Total energy preserved.

Eq. 02 — Voltage unbalance factor (NEMA) — · NEMA MG 1 §14.36
VUFNEMA=maxViVavgVavg×100%\text{VUF}_{NEMA} = \frac{\max\,|V_{i} - V_{avg}|}{V_{avg}} \times 100\%
V_avg
(V_a + V_b + V_c) / 3, V
Eq. 03 — Voltage unbalance factor (IEEE) — · IEEE Std 1159
VUFIEEE=V2V1×100%\text{VUF}_{IEEE} = \frac{|V_{2}|}{|V_{1}|} \times 100\%
V₁
positive-sequence magnitude, V
V₂
negative-sequence magnitude, V

NEMA is simple — needs only magnitudes. IEEE is rigorous — needs angles too but gives the actual ratio of harmful negative-sequence to useful positive-sequence. Use IEEE for motor derate calculations; NEMA for quick on-site checks.

Eq. 04 — NEMA MG 1 motor derate factor — · NEMA MG 1 §14.36
Fderate12(VUF%)2/100F_{derate} \approx 1 - 2 \cdot (\text{VUF}\,\%)^{2} / 100
F_derate
multiply nameplate HP by this, —

Empirical fit: a 2 % unbalance derates a 100 hp motor to ~92 hp; a 4 % unbalance derates to ~68 hp. Operate motors above 5 % unbalance only with prior approval from the manufacturer.

How to diagnose unbalance, step by step

  1. Measure all three phase-to-neutral voltages. Use a 3-phase recording meter (Fluke 1738, Dranetz HDPQ) to capture magnitude and phase angle of each line-to-neutral voltage simultaneously. A simple multimeter measures only magnitude — not enough; angles between phases matter.
  2. Pick V_a as the angular reference. Set V_a angle = 0°. Express V_b and V_c as offsets from this reference. Ideally V_b = −120°, V_c = +120°. Real measurements deviate by a few degrees, which is what unbalance analysis captures.
  3. Compute the three sequence components. V₀ (zero-sequence) = ⅓ × (V_a + V_b + V_c). V₁ (positive-sequence) = ⅓ × (V_a + a·V_b + a²·V_c). V₂ (negative-sequence) = ⅓ × (V_a + a²·V_b + a·V_c). Where a = e^(j·120°). The calculator does this automatically.
  4. Read the voltage unbalance factor. NEMA: VUF = max deviation from average / average × 100. IEEE: VUF = |V₂| / |V₁| × 100. NEMA is easier with a simple voltmeter; IEEE is more rigorous and is what motor derate tables use.
  5. Check NEMA MG 1 motor derate. NEMA MG 1 §14.36: motors must be derated by ~5 % at 3 % unbalance, ~25 % at 5 % unbalance. Negative-sequence currents heat the rotor without contributing to torque — directly causing premature insulation failure.
  6. Find and fix the source. Sources of unbalance: single-phase loads connected to one phase only, broken transformer winding, single-phase loss (open phase), unequal cable impedance, regenerative loads. Once identified, redistribute single-phase loads across all three phases or repair the open path.

NEMA MG 1 unbalance derate table

VUF (%)Motor derate factorRecommendation
01.00Perfect balance — operate at full nameplate
10.98Acceptable for continuous operation
20.95Within NEMA limit; periodic monitoring
30.88Significant derating required; investigate cause
40.82Excessive — motor lifetime reduced 50 %+
50.75Maximum allowable — replace, redistribute, or stop
> 5Operation prohibited per NEMA MG 1

Worked example: unbalanced commercial bus

Measurements at a commercial 230/400 V bus: V_a = 230 ∠0°, V_b = 220 ∠−118°, V_c = 235 ∠122°. Compute symmetrical components and recommend action.

StepCalculationResult
V_avg(230 + 220 + 235) / 3228.3 V
Max deviation|220 − 228.3|8.3 V
VUF (NEMA)8.3 / 228.3 × 1003.6 %
V₀ via Fortescuecomplex sum / 3~ 4 ∠65°
V₁ positive-sequence~ 228 ∠ 1°
V₂ negative-sequence~ 8 ∠ −80°
VUF (IEEE)8 / 228 × 1003.5 %
Motor derate (NEMA MG 1)~ 0.85 at 3.6 % VUF−15 % capacity
ActionInvestigate single-phase load distribution; aim < 2 % VUF

Variants and special cases

Single-phasing (open-phase fault)

One supply phase opens (blown fuse, broken cable, contact failure). The motor tries to run on 2 phases; voltage unbalance jumps to 33 %+. Motor draws 2–3× rated current and burns out in minutes unless thermal overload trips. Most expensive single failure mode in 3-phase systems — modern motor protectors include phase-loss detection.

Sequence components for fault analysis

Symmetrical components originally derived for short-circuit analysis (Fortescue 1918). Modern protection relays compute sequence currents continuously: ground faults show up as I₀ > threshold, phase-to-phase faults show up as I₂ > threshold, while normal balanced load shows only I₁. Each sequence has its own protection function.

Negative-sequence-only protection

ANSI Function 46 (negative-sequence overcurrent / unbalance protection) trips when I₂ exceeds a setpoint, protecting motors from sustained unbalance. Common settings: pickup at 5–10 % I_FL, trip at 30–60 seconds. Required by NEC 430.36 for large motors.

Fortescue\'s original derivation

A system of n alternating-current vectors of any character may be represented by n systems of symmetrical vectors. In a three-phase system, three sets are required: a positive-sequence, a negative-sequence, and a zero-sequence system. The mathematical treatment is greatly simplified, particularly in the analysis of unbalanced and asymmetric short-circuit conditions, by this transformation.

Fortescue, C.L. — Method of Symmetrical Co-ordinates Applied to the Solution of Polyphase Networks → Transactions of the AIEE, Vol. 37 Part II, June 1918, pp. 1027–1140

Related calculators

Frequently asked questions

What is voltage unbalance in 3-phase?
A condition where the three phase voltages are not equal in magnitude or are not exactly 120° apart. Even small imbalances (1–2 %) significantly heat induction motors because of the negative-sequence currents. NEMA defines a simple metric (max deviation from average); IEEE uses the more accurate symmetrical components ratio.
What are V₀, V₁, V₂?
The three "symmetrical components" of an unbalanced phasor set. V₀ (zero-sequence) — three equal voltages all in phase, sums to non-zero only when there's ground-current flow. V₁ (positive-sequence) — three balanced voltages 120° apart in normal phase rotation, this is the "useful" component. V₂ (negative-sequence) — three balanced voltages 120° apart in REVERSE rotation, causes counter-torque and heating in motors.
How do I calculate the voltage unbalance factor?
NEMA method: VUF = (max deviation of any single phase from the 3-phase average) / (3-phase average) × 100 %. Easy with three readings. IEEE method: VUF = |V₂| / |V₁| × 100 %. More rigorous; requires phase angles too. The two metrics agree at low imbalance and diverge slightly above ~3 %.
Why do unbalanced voltages damage motors?
Negative-sequence voltage produces a backward-rotating field in the motor air gap. This creates a counter-torque (small loss) and high-frequency rotor currents (large heating). At 3 % voltage unbalance, the negative-sequence currents can be 6–10× the rated rotor current — the rotor heats up but the torque output barely changes. Result: insulation degrades 2–3× faster, bearings fail prematurely.
What causes 3-phase voltage unbalance?
Single-phase load distribution — most common cause; when 1-φ loads are not balanced equally across three phases. Single-phasing — a blown fuse or open phase on the supply leaves the motor running on 2 phases (massive imbalance, motor burns out in minutes). Asymmetric impedance — different cable lengths or cross-sections per phase. Utility issues — unbalanced primary distribution feeders.
What is the maximum acceptable unbalance?
NEMA recommends ≤1 % for sustained operation of motors; tolerable up to 3 % with derate; never above 5 %. IEEE 1159 categorises voltage unbalance as a "long-duration variation" with limits of 0.5–2 %. ANSI C84.1 sets utility-supplied unbalance at the service point to 3 % maximum. Modern PFCs and converters add their own limits — check equipment specs.
How does NEMA MG 1 derate motors for unbalance?
NEMA MG 1 §14.36 publishes a derating curve: at 1 % VUF derate to 0.98 of nameplate; at 2 %, 0.95; at 3 %, 0.88; at 4 %, 0.82; at 5 %, 0.75 — and operation above 5 % is not recommended. Always pair the curve with a thermal protection device (NEMA Class C trip on overload).
What is the "a" operator in symmetrical components?
A complex unit-magnitude phasor at 120° angle: a = e^(j·2π/3) = −0.5 + j·0.866. Multiplying any phasor by a rotates it by 120° counter-clockwise. The Fortescue transformation matrix uses 1, a, and a² to extract each sequence from the original three phasors. a³ = 1, a² = e^(j·240°) = a*.

Sources and methodology

  1. Fortescue, C.L. Method of Symmetrical Co-ordinates Applied to the Solution of Polyphase Networks. Trans. AIEE, Vol. 37, June 1918.
  2. IEEE. IEEE Std 1159 — Recommended Practice for Monitoring Electric Power Quality, 2019.
  3. NEMA. NEMA MG 1 — Motors and Generators, 2021. § 14.36 voltage unbalance.
  4. ANSI. ANSI C84.1 — Electric Power Systems and Equipment Voltage Ratings (60 Hz), 2020.
  5. Anderson, P.M. Analysis of Faulted Power Systems, IEEE Press, 1995. Chapter 2 — symmetrical components.